Flow Test a Fire Hydrant

Reference Number: MTAS-1901
Tennessee Code Annotated
Reviewed Date: November 10, 2017
Printer-friendly versionSend by emailPDF Version

Many fire departments and water utilities do not know how to flow a fire hydrant properly. According to TDEC, there is no state regulation on how to flow a fire hydrant, but TDEC recognizes the American Water Works Association (AWWA) pamphlet # M-17 as the recognized standard for testing fire hydrants. Pamphlet M-17 is what both ISO and NFPA recognize as the approved method for flowing fire hydrants.

According to this standard, the proper way to test a hydrant and water main is to put a cap gauge on the test hydrant and take a static reading. Then proceed down stream to the next flow hydrant and back up stream to the closest flow hydrant and flow both at the same time.  Use as many ports and sizes of discharges to make the largest drop in residual pressure.  Record the pitot pressure at each flowing port and then record the residual pressure back at the test hydrant.

When the test is complete, five pieces of data will be used in determining the flow of the hydrant: the static pressure, the residual pressure, the flow (pitot) pressure, the size of the outlet flowing water, and the number of outlets open during the test.  This information will be converted to gallons per minute by using a calculator or flow chart. The residual pressure will need to be charted to record the flow in gpm at 20 psi.

According to water experts, the multi-hydrant flow test method is the best and most accurate way to conduct a test.  Doing single hydrant flow tests (i.e. where one hydrant is used to get the static, residual, and pitot pressures) is one reason so many communities seem to have so many red top hydrants.  ISO will not recognize a single hydrant flow test.